Closed Cooling Tower Need To Consider The Problem Of Anti-freezing

Sep 15, 2023

Closed  cooling  tower  need  to  consider  the  problem  of  anti-freezing .

           In  the  northern  winter , the  comperature  is  usually  lower  than  zero , and  the  operation  of  the  closed  cooling  tower  is  becoming  increasingly  prominent . If  not  properly  addressed , the  heat  exchange  tube  or  other  components  of  the  cooling  tower  may  be  frozen . According  to  different  process  characteristics , some  closed  cooling  towers  run  all  day  in  winter , some  run  during  certain  time  periods , and  others  are  hardly  used . But  everyone  needs  to  think  about  winterization .

           1. If  the  closed  cooling  tower  does  not  need  to  be  operated  in  winter , the  spray  water  and  internal  circulating  water  must  be  drained  in  the  winter  when  it  is  basically  not  used . It  is  recommened  to  use  compressed  air  to  force  the  internal  circulating  water  with  a  pressure  greater  than  4 kg , and  it  is  not  recommended  to  use  carbon  steel  tube  heat  exchangers  for  drainage .

           2. Anti-freezing  operation  in  part  time .

               Closed  cooling  tower  antifreeze   has  two  parts : spray  system  and  internal  circulating  water  system (softened  water ) .

               The  antifreeze  problem  of  the  spray  water  system  usually  adds  an  electric  heater  to  the  water  tray , which  uaually  turns  on  when  the  spray  water  is  below  5  degrees  Celsius  and  stops  above  8  degrees  Celsius . The  temperature  probe  transmits  the  signal  to  the  control  cabinet  and  antomatically  controls  the  start  and  stop  of  the  electric  heater . The  power  selection  of  the  electric  heater  is  determined  according  to  the  circulating  water  volume  and  the  external  temperature .

               Ethylene  glycol  solution  or  electric  heating  equipment  can  be  used  to  protect  the  internal  circulating  water  system  from  freezing . The  freezing  temperature  of  the  glycol  solution  should  be  lower  than  the  local  temperature .

               For  large  cooling  system  occasions , you  can  consider  digging  a  pool  to  spray  water  into  it , which  can  save  the  power  consumption  cost  of  electric  heating  operation , and  you  can  also  put  medicine  in  the  pool  to  improve  the  water  quality  of  the  spray .

           3. Frost  protection  for  year-round  operation .

               Closed  cooling  towers  that  operate  all  year  round , if  equipped  with  electrical  control  system , may  cause  changes  in  the  number  of  cooling  towers  due  to  changes  in  the  load  of  the  main  system , so  it  is  also  necessary  to  consider  the  problem  of  antifreeze . Unused  equipment  can  be  emptied  before  winter .